Fig. 6).
Item Field Range Description
Setting
1 to 8
MODE
Select the operating mode for the control.
PId or P
STAGE MODE
Select the staging operation to be either
automatic or manual.
(PId = automatic)
(P = proportional)
OFF,
70 to 220°F
(21 to 104°C)
BOILER TARGET
Select the boiler target temperature while
a setpoint demand is present.
120 to 230°F
(49 to 110°C)
BOILER OUTLET MAXIMUM
Select the maximum boiler outlet
temperature. Exceeding this temperature
shuts o the burners.
120 to 230°F
(49 to 110°C),
OFF
BOILER MAXIMUM
Select the maximum boiler target
temperature.
OFF,
80 to 180°F
(27 to 82°C)
BOILER MINIMUM
Select the minimum boiler target
temperature.
0:00 to 3:00 min
(1 second
increments)
FIRE DELAY
Select the amount of time required for
combustion pre-purging, ignition and the
ame to be established.
Note: This setting is only available when
STAGE MODE is set to Pld.
1 (Lo) or
2 (Med) or
3 (Hi)
BOILER MASS
Select the thermal mass of the boiler.
Note: This setting is only available when
STAGE MODE is set to PId.
Au, 0:30 to
9:55 min
STAGE DELAY
Select the minimum time delay between
stages.
Note: This setting is only available when
STAGE MODE is set to PId.
Au, 2 to 42°F
(1 to 23°C)
DIFFERENTIAL
Select the boiler dierential.
Note: The automatic setting is only available
when STAGE MODE is set to PId staging.